ClimateFleet reference stack ​

Bench test

Primary path (P1 XY-MD02 + 4G DTU): bench tested. Other profiles: pending.

Fleet dashboard for temperature and humidity sensors. Device type: ht_sensor.

Dashboard notes: ClimateFleet (dashboard).


Telemetry contract ​

KeyUnitTypical range (indoor)
temperature°CAbout 18–32 (comfort); alarms per profile
humidity%RHAbout 35–75

Reference sensor (bench tested — P1) ​

ItemDetail
SensorXY-MD02 RS485 Modbus temperature & humidity probe
Datasheet / mapFactory default 9600 8N1, slave ID often 1 — holding registers for temp/RH (see DR154 guide register table)
EnvironmentIndoor / duct mount per probe rating

Connectivity options ​

ProfileGuideStatus
P1 4G DTUDR154 + XY-MD02Bench tested
P2 ESP32 WiFiESP32 Modbus edge with XY-MD02 mapPending bench test
P4 Native WiFi sensorMQTT JSON with temperature / humidityBYO

Wiring — P1 ​

mermaid
flowchart LR
  AC[Autoconnecto]
  GW[htgateway]
  DTU[4G DTU]
  XY[XY-MD02 RS485]
  AC --> GW
  GW <-->|MQTT| DTU
  DTU --> XY
RS485Notes
PowerPer XY-MD02 manual (often 5–24 V DC)
A/BTo DTU; confirm polarity
Termination120 Ω if long bus

Wiring — P2 (lab / office WiFi) ​

mermaid
flowchart LR
  AC[Autoconnecto MQTT]
  ESP[ESP32 + MAX485]
  XY[XY-MD02]
  AC <--> ESP
  ESP --> XY

Use the same Modbus addresses as the DR154 child map; publish JSON to device token.


Autoconnecto checklist ​

  • [ ] Create gateway + child devices linked with parentDeviceId (Sample On demos this topology)
  • [ ] Child device type ht_sensor
  • [ ] Child on Modbus gateway (P1) or direct MQTT device (P2/P4)
  • [ ] Keys exactly temperature, humidity on the child
  • [ ] Optional hub health: publish gateway.heartbeat on the gateway token (no childDeviceId)
  • [ ] Gateway shows Active from hub heartbeat and/or any active child

support@autoconnecto.in · founder@autoconnecto.in · +91 92121 00555 · app.autoconnecto.in