Appearance
ClimateFleet reference stack
Bench test
Primary path (P1 XY-MD02 + 4G DTU): bench tested. Other profiles: pending.
Fleet dashboard for temperature and humidity sensors. Device type: ht_sensor.
Dashboard notes: ClimateFleet (dashboard).
Telemetry contract
| Key | Unit | Typical range (indoor) |
|---|---|---|
temperature | °C | About 18–32 (comfort); alarms per profile |
humidity | %RH | About 35–75 |
Reference sensor (bench tested — P1)
| Item | Detail |
|---|---|
| Sensor | XY-MD02 RS485 Modbus temperature & humidity probe |
| Datasheet / map | Factory default 9600 8N1, slave ID often 1 — holding registers for temp/RH (see DR154 guide register table) |
| Environment | Indoor / duct mount per probe rating |
Connectivity options
| Profile | Guide | Status |
|---|---|---|
| P1 4G DTU | DR154 + XY-MD02 | Bench tested |
| P2 ESP32 WiFi | ESP32 Modbus edge with XY-MD02 map | Pending bench test |
| P4 Native WiFi sensor | MQTT JSON with temperature / humidity | BYO |
Wiring — P1
mermaid
flowchart LR
AC[Autoconnecto]
GW[htgateway]
DTU[4G DTU]
XY[XY-MD02 RS485]
AC --> GW
GW <-->|MQTT| DTU
DTU --> XY| RS485 | Notes |
|---|---|
| Power | Per XY-MD02 manual (often 5–24 V DC) |
| A/B | To DTU; confirm polarity |
| Termination | 120 Ω if long bus |
Wiring — P2 (lab / office WiFi)
mermaid
flowchart LR
AC[Autoconnecto MQTT]
ESP[ESP32 + MAX485]
XY[XY-MD02]
AC <--> ESP
ESP --> XYUse the same Modbus addresses as the DR154 child map; publish JSON to device token.
Autoconnecto checklist
- [ ] Create gateway + child devices linked with
parentDeviceId(Sample On demos this topology) - [ ] Child device type
ht_sensor - [ ] Child on Modbus gateway (P1) or direct MQTT device (P2/P4)
- [ ] Keys exactly
temperature,humidityon the child - [ ] Optional hub health: publish
gateway.heartbeaton the gateway token (nochildDeviceId) - [ ] Gateway shows Active from hub heartbeat and/or any active child