WaterFleet reference stack ​

Bench test

Pending bench test — Validation status.

Fleet dashboard for water flow and pressure. Device type: water_meter.


Telemetry contract ​

KeyUnitTypical use
flow_ratem³/h or L/min (document on device)Instantaneous flow
total_volume_m3m³Integrator / totalizer register
pressure_barbarLine or outlet pressure transducer

Align Modbus scale factors with manufacturer manuals (pulse constants for totalizer).


Reference hardware (pending bench test) ​

ItemDetail
FlowElectromagnetic flow meter with Modbus RTU (e.g. compact DN50 class meters — confirm register map in vendor manual)
Pressure4–20 mA or Modbus pressure transmitter 0–10 bar class (map to pressure_bar)
DatasheetUse vendor communication protocol appendix for register addresses and float/word order

Status: Pending bench test — two Modbus slaves on one RS485 bus (flow + pressure) or one integrated meter if it exposes all keys.


Connectivity options ​

ProfileEdgeLinkStatus
P14G DTUCloud Modbus masterPending bench test
P2ESP32 / edge GWWiFi or EthernetPending bench test
P3Modbus TCP at pump roomEthernetPending bench test

Wiring — P1 / P2 (RS485 bus) ​

mermaid
flowchart TB
  subgraph Field
    EM[Electromagnetic flow meter]
    PT[Pressure transmitter]
  end
  subgraph Edge
    EDGE[DTU or ESP32 master]
  end
  AC[Autoconnecto]
  EM -->|RS485| EDGE
  PT -->|RS485| EDGE
  EDGE <-->|MQTT| AC
BusNotes
RS485Unique slave IDs; common baud (often 9600); termination at ends
Flow installStraight pipe run per EM meter datasheet (upstream/downstream lengths)
PressureTap location per hydraulic design; isolate for service

Modbus mapping (conceptual) ​

Map from vendor manual — example pattern only:

Telemetry keyTypical source
flow_rateInstantaneous flow register × scale
total_volume_m3Totalizer (32-bit or float pair)
pressure_barPressure register in bar or kPa × scale

Autoconnecto checklist ​

  • [ ] Create gateway + child devices linked with parentDeviceId (Sample On demos this topology)
  • [ ] Child device type water_meter per site or per meter set (one device publishing all three keys)
  • [ ] Units consistent with dashboard labels; telemetry on the child
  • [ ] Optional hub health: publish gateway.heartbeat on the gateway token
  • [ ] Gateway shows Active from hub heartbeat and/or any active child
  • [ ] Spike-friendly ranges in alarms (burst flow vs leak)