EnergyFleet reference stack ​

Bench test

Primary path (P1 AVH + 4G DTU): bench tested. Other profiles (P2–P4): pending. Tracker: Validation status.

Fleet dashboard for 3-phase energy meters. Device type: energy_meter.

Dashboard spine: Solution dashboard template.


Telemetry contract ​

Keys consumed by EnergyFleet widgets (align published telemetry to these names):

KeyTypical unitSource (AVH-14-M1 manual)
active_power_kw_total, active_power_kw_l1…l3kWPer-phase and total active power
voltage_l1n … voltage_l3n, voltage_l12 …VL–N / L–L
current_l1 … current_l3, current_avgAPhase current
frequency_hzHz45–60 Hz band per meter spec
power_factor_avg, power_factor_l1…—0.1–1.0
energy_kwh_int, energy_kwh_frackWhInteger + fraction pair per AVH note
md_kw, load_hourskW, hDemand / run hours

Sample generators and alarms in Autoconnecto use field-realistic bands derived from the AVH-14-M1 Modbus map.


Reference sensor (bench tested — P1) ​

ItemDetail
MeterMultispan AVH-14-M1 multifunction energy meter
DatasheetAVH-14-M1 manual — Modbus float, 32-bit CDAB, FC3 holding registers
InstallPanel mount; CT/VT programming per manual (qualified electrician)

Connectivity options ​

ProfileLinkStatus
P1 4G DTU + RS485AVH-14-M1 + DR154 MQTTBench tested
P2 ESP32 WiFi edgeESP32 Modbus edge — implement AVH register map in firmwarePending bench test
P3 Ethernet Modbus TCPGateway DIRECT to serial server at panelPending bench test
P4 Native MQTT meterOnly if meter publishes keys above nativelyBYO

Wiring — P1 (cloud Modbus, 4G) ​

mermaid
flowchart LR
  AC[Autoconnecto]
  GW[energygateway MQTT_SERIAL]
  DTU[4G DTU]
  AVH[AVH-14-M1 RS485]
  CT[CTs on feeders]
  AC --> GW
  GW <-->|MQTT| DTU
  DTU --> AVH
  CT --> AVH
StepAction
1Install meter + CT/VT per AVH-14-M1 terminal diagram (mains work)
2RS485 A/B to DTU; baud 9600 8N1 (match meter menu)
3Create energygateway + child avh1 with AVH register map (see device guide)
4Configure DTU MQTT topics with gateway token

Wiring — P2 (ESP32 WiFi at panel) ​

Same RS485 to AVH; ESP32 replaces DTU for MQTT uplink on WiFi. Reuse register addresses from AVH device guide.


Autoconnecto checklist ​

  • [ ] Create gateway + child devices linked with parentDeviceId (Sample On demos this topology)
  • [ ] Child device type energy_meter
  • [ ] Modbus map matches AVH float CDAB addresses
  • [ ] Telemetry visible on child device, not only gateway
  • [ ] Optional hub health: publish gateway.heartbeat on the gateway token (no childDeviceId)
  • [ ] Gateway shows Active from hub heartbeat and/or any active child