CoolingTowerFleet ​

Bench test

Pending — Validation status.

White-label ready cooling-tower fleet (catalog title CoolingTowerFleet; OEM label e.g. COOLFAB SMART TOWER on SERVER attribute white_label). Device type cooling-tower. Profile name Cooling Tower.

Sample On provisions eight towers across Customer A / B / C (MP, Gujarat, Maharashtra — one SITE asset + scoped demo user each) with a physically consistent simulator (wet-bulb peak ~14:00–15:00 IST, per-tower duty cycles, recoverable faults, motor electrics at 70–90% FLC). Sign in as a customer demo user to see shared-dashboard isolation on the same dashboard. Use copies the dashboard, SCADA board, and throttled-notify rule engine without demo devices, generators, demo users, or sample history — create your own customer assets the same way. The fleet map uses lat/long with alarm colouring; the SCADA mimic binds to the Selected cooling tower alias.

SERVER attributes (per tower) ​

AttributeMeaning
tower_modelModel plate (e.g. COOLFAB SMART TOWER CT-100)
capacity_trDesign tons refrigeration
cellsCell count
motor_hp / motor_flc_a / ct_ratioFan motor
design_inlet_c / design_outlet_c / design_flow_m3hDesign thermal
pipe_dn / basin_depth_mHydraulics
approach_warn_c / approach_crit_c / approach_low_cApproach high/low limits (°C); low only while motor running
current_high_fla_pctOvercurrent trip as % of motor_flc_a (default 90)
vibration_warn_mm_s / vibration_crit_mm_sISO 10816-style bands
basin_low_pctLow-basin trip
maintenance_interval_hours / last_service_dateService planning
customer_label / white_labelTenant / OEM labels
duty_cyclealways (24 h), two_shift, or day_only

Telemetry keys ​

KeyUnitNotes
inlet_temp_c / outlet_temp_c°CProcess water
range_c°Cinlet − outlet
approach_c°Coutlet − wet bulb
wet_bulb_c / ambient_temp_c°CSite climate
voltage_r / voltage_y / voltage_bV400–430 band
current_r / current_y / current_bA~70–90% FLC when ON
current_fla_pct%Max phase current / FLC × 100
power_kw / pf / frequency_hzkW / — / Hz√3·V·I·PF
energy_kwh / running_hourskWh / hMonotonic while motor_on
motor_onboolFan / CW pump run
vibration_mm_smm/sWarn 4.5 / crit 7.1
flow_m3hm³/h~0 when motor OFF
basin_level_pct%Makeup / evaporation
signal_rssidBmLink quality
sensor_faultcodePT100 / 4–20 mA fault — inlet omitted (not 999)
phase_imbalance_pct%Max−min phase current / avg
motor_no_flow0/1Motor ON with ~0 flow
latitude / longitude°Fleet map

Alarms ​

Profile alarm rules (self-clearing) use DYNAMIC thresholds: stage percentages of SERVER limit attributes (approach_crit_c, approach_low_c, current_high_fla_pct, inlet_high_c, vibration_crit_mm_s, basin_low_pct, maintenance_interval_hours, …) seeded per Sample device. Cover high/low approach, motor overcurrent (FLA %), high inlet, range high/low, vibration, voltage band, low basin, sensor fault, phase imbalance, motor-no-flow, maintenance hours, and offline (NO_UPDATE on signal_rssi).

Low approach and low range use suppressWhen motor_on is_false so they only raise while the motor is running (stopped towers publish range_c = 0). While sensor_fault is active (PT100 open), inlet is omitted from the payload and inlet-high / range-high are suppressed so averages stay clean and the demo shows a clean sensor-fault raise/clear. Energy kWh and running hours are monotonic across Sample restarts. Customer B CT-2 periodically runs a few minutes above 90% FLA so the overcurrent alarm can be shown live.

Sample attaches rule engine Cooling Tower Alarms (throttled email notify for every VALUE alarm) to the Cooling Tower demo profile. Use copies that engine — attach it to your Cooling Tower profile when you want chain-side notify in addition to profile alarms; do not duplicate the same threshold on both without reason.

Dashboard states ​

StateContents
Fleet homeActive / inactive / all counts → list states; alarm summary + table; map; SCADA mimic; service due
List statesDevice table → tower detail
Tower detailSCADA (fan spins on motor_on, basin level), gauges (inlet/outlet/range/approach), motor electrics, vibration / flow / energy / hours trends, device alarms, service due

Customer tenants see the same states scoped to their devices after Use + binding.

Reports ​

Sample On creates daily and monthly tower-performance reports (approach_c, range_c, energy_kwh, running_hours) plus daily/monthly alarm-count schedules. After Use, create your own (or clone the pattern):

  • Schedule daily or monthly
  • Aggregation avg (temps) / leave raw or sum for counters as required
  • Format CSV (download or email). PDF: print the CSV/report view or use your document tool — the Reports module ships CSV.

Connectivity ​

P2 edge gateway Modbus TCP / RTU to VFD + instruments · P3 plant Ethernet · P1 4G DTU for remote sites · P4 OEM cloud if the tower controller already publishes MQTT.